Iterative Interpolated DFT-based Frequency Estimator for Electrical Waveform Affected by Decaying DC Offset - Laboratoire de l'intégration, du matériau au système TOUS LABOS Accéder directement au contenu
Communication Dans Un Congrès Année : 2022

Iterative Interpolated DFT-based Frequency Estimator for Electrical Waveform Affected by Decaying DC Offset

D. Belega
  • Fonction : Auteur
D. Petri
  • Fonction : Auteur

Résumé

An iterative Interpolated Discrete Fourier Transform (IpDFT)-based frequency estimator of a sinewave affected by decaying dc offset is proposed in this paper. The accuracies of the proposed procedure and the classical IpDFT algorithm are compared with each other under different steady-state and dynamic testing conditions suggested in the IEC/IEEE 60255-118.1:2018 - Synchrophasors for power systems – Measurements. A decaying dc offset is added to the test signals suggested in the Standard and off-nominal frequency is considered. Procedure accuracy is analyzed through simulations by considering the maximum of the absolute value of the frequency error. Comparison with the frequency error thresholds proposed in the Standard is also performed.
Fichier principal
Vignette du fichier
IMS_IMEKO_2022_Belega.pdf (250.23 Ko) Télécharger le fichier
Origine Fichiers éditeurs autorisés sur une archive ouverte

Dates et versions

hal-04572244 , version 1 (10-05-2024)

Identifiants

Citer

D. Belega, D. Petri, Dominique Dallet. Iterative Interpolated DFT-based Frequency Estimator for Electrical Waveform Affected by Decaying DC Offset. 25th IMEKO TC4 International Symposium, Sep 2022, Brescia, Italy. pp.266-270, ⟨10.21014/tc4-2022.49⟩. ⟨hal-04572244⟩